Duct Leakage Testers

PRODUCT DETAILS

Positive and Negative Duct Accreditation (PANDA) System

The Positive and Negative Duct Accreditation (PANDA) system provides contractors, commissioning engineers, and research and development technicians with the best in class choice of test equipment to quantify air leakage in ductwork and other areas as well as the ability to measure the performance of ducted systems. The PANDA provides a fast, accurate, automated solution and helps to ensure compliance with EN12237, EN1507, EUROVENT 2/2 and SMACNA standards, enhancing energy savings in buildings.


Features and Benefits

• Positive and Negative Duct Leakage Testing in one rig

• Energy savings by testing and minimizing duct leaks

• Compliant with the following standards:

– EN12237 Ventilation for Buildings—Ductwork

Strength and Leakage of Circular Sheet Metal Ducts

– EN1507 Ventilation for Buildings—Sheet Metal ducts with

Rectangular Section—Requirements for Strength

and Leakage

– EUROVENT 2/2 Air Leakage Rate in Sheet Metal Air

Distribution Systems

– SMACNA Air Duct Leakage Testing

• Accuracy is ± 2,5% of volume flow

• Unique performance and fan speed control charge up of

duct system to test static pressure within minutes

• Carry weight 45 kg (99 lbs.)

• Fits in the back of vans and estate cars

• Model PAN341 comes with standard Airflow TA465-P

Multi-Function Instrument and PVM610 Micromanometer.

– Automatically calculates leakage rate in real time

– Simultaneous displays flow leakage rate and static pressure

– Provides a pass/fail indication for a given tightness class

– Automatically corrects actual volume flow leakage rate

to Standard Temperature and Pressure (STP)

– Monitors barometric pressure and temperature

in real time

– Stores data that can be downloaded for report

generation and documentation

– Works with Model 8934 Portable Printer



Specifications

Model PAN341 Series

Pressure Measurement (PVM610)

Range ± 3,735 Pa (± 15 in. W.G.)

Resolution 0.1 Pa (0.001 in. W.G.)

Accuracy 1% of reading ± 1 Pa (± 0.005 in. W.G.)

Actual Duct Static Range ± 2,500 Pa (± 10 in. W.G.) at Zero Flow

Volume Flow Measurement (TA465-P)

Wilson Radial Flow Grid High leakage range: 10 to 200 l/s (36 to 720 m3/hr, 21 to 424 cfm)

15 mm Conical Inlet Nozzle Adapter

Low leakage range: 1 to 13 l/s

(3.6 to 46.9 m3/hr, 2 to 27.5 cfm)

Resolution 0.01 l/s (0.01 m3/hr, 0.01 cfm)

Accuracy ± 2.5% of reading ± 0.01 l/s

(± 0.04 m3/hr, ± 0.02 cfm)

Temperature Measurement (TA465-P)

K Type thermocouple probe To EN60584 (IEC 584)

Barometric Pressure Measurement (TA465-P)

Range 690 to 1,241 hPa (517.5 to 930.87 mm Hg,

20.36 to 36.648 in. Hg)

Accuracy ± 2% of reading